Bill of Materials View BOM
Copper Ground Plate - Copper Conductor
Copper Ground Plate - Copper Conductor

Part No.
Ground Plate Size
Conductor
(AWG)
Approx. Each
Wt. (lbs.)
Add to BOM ◆
GP18182T
18" x 18"
2T
4
Add to BOM ◆
GP18184/0
18" x 18"
4/0
4-1/2
Add to BOM ◆
GP24242T
24" x 24"
2T
6-1/2
Add to BOM ◆
GP24244/0
24" x 24"
4/0
7
◆ BOM = Bill of Materials
• Copper Ground Plate features an 18" or 24" (depending on the size of the
plate) copper conductor exothermically welded to the plate.
• Thickness is .032 inches.

TECHNICAL NOTES:
NEC 2014 Article 250.52(A)(7) (Summarized)
   Each plate electrode shall expose not less than 0.186 m2 (2 ft2) of surface to exterior soil. Electrodes
   of non-ferrous metal shall be at least 1.5 mm (0.06 in.) in thickness.
NEC 2014 Article 250.53 (A)
   Rod, Pipe, and Plate Electrodes. Where practicable, rod, pipe and plate electrodes shall be embedded
   below permanent moisture level. Rod, pipe and plate electrodes shall be free from nonconductive
   coatings such as paint or enamel.
APPLICATION NOTES:
• Copper Ground Plates are used in areas having little or no top soil.
• Can also be used to enhance ground grid systems.
• Can be used in conjunction with earth enhancement material such as Ultrafill.
* Other sizes and thicknesses are available. Please contact factory for more information.